TRIP CIRCUIT SUPERVISION RELAY JRV 911-1

OVERVIEW

    Features

  • Sensing by electronic circuit
  • Low supervision current
  • Immune to breaker operation
  • Continuous monitoring

Application:

Trip Circuit Supervision Relay (TCSR) is used formonitoring healthiness of the circuit breaker (CB) trip circuit, CB trip coil and CB power supply. The monitoring of two trip coil circuit has to be done by only one TCSR.

TRIP CIRCUIT SUPERVISION RELAY JRV 911-1

Principle of Operation:

TCSR monitors the healthiness of the trip circuit of breaker. Basically the circuit drives a small current through the breaker trip coil and monitors it continuously. If there is any failure in the trip circuit or trip coil circuit, the relay will sense and operate it's output contacts. About 400ms delay is introduced to prevent false indication during circuit breaker operation. A test button is provided to test the relay contacts for trip and alarm in healthy condition only.

The facility for monitoring two trip coils with independent power supply is provided in one enclosure.

 

SPECIFICATIONS

Ratings:

Voltage rating

:

18 to 60V DC
20 to 260V DC

Burden

 

:

Less than 2W (non operated)
Less than 5W (Operated).

     

Settings:

Operating characteristics

:

0.03 to 0.1A in steps of 0.01A
0.3 to 1.0A in steps of 0.1A
0.03 to 0.1A in steps of 0.01A
0.15 to 0.5 in steps of 0.05A
0.3 to 1.0A in steps of 0.1A
1.5 to 5.0A in steps of 0.5A

Over Load Rating:

Current input

:

10 times the rated continuosly

     

Burden:

Auxiliary circuit

:

£ 3W ( Non-operated)
£ 6W ( operated)

Current input circuit

:

£ 2VA at rated current

     

Accuracy:

Operating time

:

Appx. 400ms

     

Contact Ratings:

Contacts

:

5A at 24V DC/ 230V AC

     
 
 

Mechanical Design:

Weight

:

Appx. 500 gms

Case Size Fascia
Installation

:
:

96mm sq, depth of 105mm
Flush mounting

Panel cutout

:

92mm x 92mm

     

Standard Compliance:

Accuracy test

:

IEC 60255-3

Insulation test

:

IEC 60255-5

     

Contact Durability:

Unloaded contact

:

1,000,000 Operations

Loaded contact

:

100,000 Operations

 
 
 

TRIP CIRCUIT SUPERVISION RELAY JRV 911-1

DOWNLOADS

TRIP CIRCUIT SUPERVISION RELAY JRV 911-1

Catalogues:

DOWNLOAD

Operating Manual:

DOWNLOAD

 

TRIP CIRCUIT SUPERVISION RELAY JRV 911-1

 

ORDERING INFO.

Ordering Information:

Relay type

:

JRV 911-1

Voltage rating

:

18 to 60V DC
20 to 260V DC

 

TRIP CIRCUIT SUPERVISION RELAY JRV 911-1

 