AUTO RECLOSE RELAY WITH FAST RESET JRV 142

OVERVIEW

    Features

  • Software based design
  • Built- in Auto / Manual selection facility
  • Fast reset facility
  • No. of shots selectable
  • High accuracy and stability
  • Drawout case

Application:

The auto reclose function is normally used in feeder protection relays that are protecting an overhead line. Most of the overhead line faults are temporary in nature. Even 85% can be cleared by using the auto reclose function.

AUTO RECLOSE RELAY WITH FAST RESET JRV 142

Principle of Operation:

The relay receives the fault initiation from the protection relay and that triggers the auto reclose function. After tripping the circuit breaker (CB), the Auto reclose function can reclose the CB. Normally , the first reclose (or shot) is so short in time that consumer cannot notice anything . However the fault is cleared and the feeder will continue in normal service. Even though the basic principle of Auto reclose is simple, there are a lot of different timers and parameters that have to be set.

 

SPECIFICATIONS

Ratings:

No. of shots

:

4shot, 2shot, 1shot

Aux. Supply

:

30V DC
110V DC
220V DC

     

Settings:

4 - shot STD
Reclaim time


:


1 - 255s in steps of 1s

DT1, DT2, DT3, Dt4

:

0.25s - 60s in steps of 0.25s

Fast reset

:

0 - 15 s in steps of 1s

2 - shot STD
Reclaim time


:


200 - 300s in steps of 1s

Dead Time 1

:

10s - 60s in steps of 1s

Dead Time 2

:

30s - 180s in steps of 1s

Fast reset

:

0 - 15 s in steps of 1s

2 - shot
Reclaim time


:


1 - 255s in steps of 1s

Dead Time 1

:

0.25s - 60s in steps of 0.25s

Dead Time 2

:

0.25s - 60s in steps of 0.25s

1 - shot
Reclaim time


:


6 - 69s in steps of 1s

Dead Time 1

:

0.1s - 1.6s in steps of 0.1s

     

Over Load Ratings

Voltage input

:

120% of rated voltage continuously

     

Burden:

Aux. Supply

:

Less than 5W (Non operated)
Less than 7W (Operated)

     
 
 

Accuracy:

Operating Time

:

±5% or ±30ms whichever is higher

     

Contact Ratings:

TRIP / ALARM
Lockout Relay &
Reclose Relay

 

:

 

10A at 24V DC/230V AC

     

Mechanical Design :

Weight

:

2500 gms. (approx)

Case Size Fascia
Installation

:
:

144sq mm, depth 232mm
Flush mounting

Panel cutout

:

138mm x 138mm

     
 

Contact Durability :

Unloaded contact

:

1,000,000 Operations.

Loaded contact

:

100,000 Operations

     

Insulation:

  1. 2KV RMS, 50 Hz for 1 minute / 2.5 KV for 1 s . Between all terminals and cases .
  2. 1KV RMS, 50 Hz for 1 minute across open contacts
 

AUTO RECLOSE RELAY WITH FAST RESET JRV 142

 

DOWNLOADS

AUTO RECLOSE RELAY WITH FAST RESET JRV 142

Catalogues:

DOWNLOAD

Operating Manual:

DOWNLOAD

 

AUTO RECLOSE RELAY WITH FAST RESET JRV 142

 

ORDERING INFO.

Ordering Information:

Relay type

:

JRV 142

Relay rating type

:

JRV 142(4 shot Standard)
JRV 142(2 shot Standard)
JRV 142(2 shot)
JRV 142(1 shot Railways)

Aux. Supply

:

30V DC
110V DC
220V DC

 

 

 

 