Single pole, instantaneous, restricted earth fault relay
₹14,523.08
Product Code: JRD 011
Time line :Products will be shipped within 3 weeks from the date of order
Stock In Stock
Viewed 5747 times
Categories
Cart
Account
Search
Recent View
All Categories
×
-
Products Category
- Earth Leakage Relays
- Electromechanical Auxiliary & High Speed Tripping Relays
- Electronic Hooters
- LED Indicating Lamps
- LED Semaphore Indicators
- Micro Processor Based Directional / Non-directional, Non-Communicable Current Relays
- MICRO PROCESSOR BASED INSTANTANEOUS / DEFINITE TIME AC VOLTAGE RELAYS
- Micro Processor Based Multi Shot, Auto Reclose Relays
- Micro Processor Based Neutral Earth Resistor Monitoring Relays
- Micro Processor Based PT Fuse Failure Relays
- MICRO PROCESSOR BASED RESTRICTED E/F RELAYS
- Micro Processor Based Trip Circuit Supervision Relays
- Numerical Check Synchronizing Relays
- Numerical Directional / Non-directional, Non-Communicable Current Relays
- Numerical Non-directional Inverse Time Current Relays Without Communication
- NUMERICAL OVERFLUX RELAYS
- Numerical Transformer Differential Relays
- Panel Accessories
- Push Buttons
- Semaphore Indicators
- Terminal Blocks & Plugs for Testing
- Time Delay Relays
- Two Stage Frequency Relays
- Micro Processor Based Inverse Time Non- Directional, Non-communicable Current Relays
- Non-directional Inverse Time Current Relays With/without Communication
- Micro Processor Based Inverse Time Non-directional, Non-communicable Current Relays
- Micro Processor Based Instantaneous / Definite Time Ac Voltage Relays
- Micro Processor Based Instantaneous / Definite Time Battery E/F Relays
- Micro Processor Based Instantaneous / Definite Time Current Relays
- Micro Processor Based Instantaneous / Definite Time Dc Voltage Relays
Shopping Cart
×
Your shopping cart is empty!
Search
×
Recent View Products
×
Product Description
Features
- Software based design
- Very sensitive and wide setting range
- Insensitive to currents at harmonic frequencies
- Trip test facility
APPLICATION
Restricted earth fault protection of transformers,
generators and motors differential protection of bus bars,
motors and generators.
PRINCIPLE OF OPERATION
The Relay JRD 011 are current operated Microprocessor based, differential relay which work on
the high impedance principle. An external series stabilizing resistor is used with this relay to
make it a voltage operated relay. The voltage setting of the relay is adjusted to be higher than
that developed by the current transformers used for maximum external fault conditions. JRD 011
is a single pole relay.
The sensing current is converted to voltage by an internal resistor and this voltage is fed to a harmonic network which is tuned to fundamental frequency. The output of filter is fed to voltage comparator. When the sensing current signal at the fundamental frequency exceeds the set value,the comparator gates a train of pulses to the processor. The program residing in the CPU performs the function of control and also gives output signals for relay and LED driver circuits. The operation of the relay is indicated by the glowing of a 'Red' LED, which has to be reset manually by means of a 'RESET' push button provided on the front of the relay. A 'Trip Test' push button is also provided in the relay to enable testing of the trip and alarm circuits. When this push button is pressed, the output element of the relay is energized and its contacts close to energize the trip and alarm circuits.
The relay will not operated at third harmonic currents upto 25 times the setting.
The sensing current is converted to voltage by an internal resistor and this voltage is fed to a harmonic network which is tuned to fundamental frequency. The output of filter is fed to voltage comparator. When the sensing current signal at the fundamental frequency exceeds the set value,the comparator gates a train of pulses to the processor. The program residing in the CPU performs the function of control and also gives output signals for relay and LED driver circuits. The operation of the relay is indicated by the glowing of a 'Red' LED, which has to be reset manually by means of a 'RESET' push button provided on the front of the relay. A 'Trip Test' push button is also provided in the relay to enable testing of the trip and alarm circuits. When this push button is pressed, the output element of the relay is energized and its contacts close to energize the trip and alarm circuits.
The relay will not operated at third harmonic currents upto 25 times the setting.
TECHNICAL DATA RATING
SETTINGS
IMPEDENCE
EXTERNAL STABILIZING RESISTORS
OVER LOAD RATING
Burden
Accuracy
Current rating :
1A/5A
Definite time setting :
20 to 60V DC
75 to 150V DC
175 to 300V DC/185-250V AC
75 to 150V DC
175 to 300V DC/185-250V AC
Operating value :
2.5 to 80% in steps of 2.5%
1A rated :
200 milli Ohms
5A rated :
20 milli Ohms
1A rated :
0 – 600 Ohms 100W adjustable
5A rated :
0 – 100 Ohms 100W adjustable
Current input :
2 times rated continuously
20 times rated for 3s
20 times rated for 3s
Input voltage :
Less than 0.2VA at Rated 1A
Less than 0.5VA at rated 5A
Less than 0.5VA at rated 5A
Auxiliary supply :
Less than 3W(Non operated)
Less than 5W(Operated)
Less than 5W(Operated)
Operating value :
+/- 5%
Operating time :
+/- 5% or +/- 30ms
Contact Ratings
Contact Durability
Insulation
Mechanical Design
Rating :
10A at 24V DC/230V AC
Loaded contact :
10,000 operations
Unloaded contact :
20,000 operations
- 2KV RMS, 50 Hz for 1 minute/ 2.5KV FOR 1 sec.
Between all terminals and cases - 1KV RMS, 50 Hz for 1 minute across open terminals
Accuracy test :
IEC 60255-151
Insulation test :
IEC 60255-27
Weight :
Less than 1500 gms
Case size :
144 sq mm with depth of 117 mm
Installation :
Flush mounting
Panel cutout :
138 X 138 mm
Ordering Information
Relay Type :
JRD 011
Rated Current :
1A/ 5A
Auxiliary supply :
20 to 60V DC
75 to 159V DC
175 to 300V DC/185-250V AC
75 to 159V DC
175 to 300V DC/185-250V AC