Auxiliary relay with 4 pairs of H/R contacts per element(Single element relay)
₹4,647.50
Product Code: JRV 161
Time line :Products will be shipped within 3 weeks from the date of order
Stock In Stock
Viewed 4674 times
Categories
Cart
Account
Search
Recent View
All Categories
×
-
Products Category
- Earth Leakage Relays
- Electromechanical Auxiliary & High Speed Tripping Relays
- Electronic Hooters
- LED Indicating Lamps
- LED Semaphore Indicators
- Micro Processor Based Directional / Non-directional, Non-Communicable Current Relays
- MICRO PROCESSOR BASED INSTANTANEOUS / DEFINITE TIME AC VOLTAGE RELAYS
- Micro Processor Based Multi Shot, Auto Reclose Relays
- Micro Processor Based Neutral Earth Resistor Monitoring Relays
- Micro Processor Based PT Fuse Failure Relays
- MICRO PROCESSOR BASED RESTRICTED E/F RELAYS
- Micro Processor Based Trip Circuit Supervision Relays
- Numerical Check Synchronizing Relays
- Numerical Directional / Non-directional, Non-Communicable Current Relays
- Numerical Non-directional Inverse Time Current Relays Without Communication
- NUMERICAL OVERFLUX RELAYS
- Numerical Transformer Differential Relays
- Panel Accessories
- Push Buttons
- Semaphore Indicators
- Terminal Blocks & Plugs for Testing
- Time Delay Relays
- Two Stage Frequency Relays
- Micro Processor Based Inverse Time Non- Directional, Non-communicable Current Relays
- Non-directional Inverse Time Current Relays With/without Communication
- Micro Processor Based Inverse Time Non-directional, Non-communicable Current Relays
- Micro Processor Based Instantaneous / Definite Time Ac Voltage Relays
- Micro Processor Based Instantaneous / Definite Time Battery E/F Relays
- Micro Processor Based Instantaneous / Definite Time Current Relays
- Micro Processor Based Instantaneous / Definite Time Dc Voltage Relays
Shopping Cart
×
Your shopping cart is empty!
Search
×
Recent View Products
×
Product Description
Features
- Wide range of voltage configuarations
- Electromechanical design
- Hand reset contacts
- Operation annunication in the form of S/R or H/R flag
- Protective transparent cover for the element
- Compact panel mounting case
Application
- Switching functions in protection, control and alarm circuits
- Contact multiplication in tripping and signalling circuits of protection relays
- AC/DC fail supervision
Principle of Operation
The auxiliary relays are voltage operated, attracted armature type with 4 change over contacts per
element. Each element is enclosed in a dust proof moulded,transparent, polycarbonate cover.
Radio metal is used for the magnetic components such as the armature, the core and the yoke of
the auxiliary relay to ensure good electrical performance.
The contacts are made of phosphor bronze and are nickel plated. The contact tips are made of pure silver. The use of these materials ensures very good contact performance.
The contacts are made of phosphor bronze and are nickel plated. The contact tips are made of pure silver. The use of these materials ensures very good contact performance.
Rated Voltage
Relay voltage :
24,30,48,110,220,250V DC or 63.5,110 or 230V, 50 Hz AC
Opearating range :
75-120% of rated voltage for DC relays
80-115% of rated voltage for AC relays
80-115% of rated voltage for AC relays
Reset value :
Above 10% of the rated voltage
Burden :
4 watts(maximum) at rated voltage
Operating time :
Less than 25 ms at rated voltage(nominal)
Reset time :
Less than 10 ms
Opeation indicator :
a)self reset flag or
b)hand reset flag or
c)hand reset reverse flag for AC/DC fail indication or
d)no flag
b)hand reset flag or
c)hand reset reverse flag for AC/DC fail indication or
d)no flag
CONTACT RATING
Make & Carry continuous :
2500 VA with maximum of 5 A and 660V AC
2500 W with maximum of 5 A and 660V DC
2500 W with maximum of 5 A and 660V DC
Make & Carry for 3sec :
7500 VA with maximum of 30 A and 660V AC
7500 W with maximum of 30 A and 660 V DC
7500 W with maximum of 30 A and 660 V DC
Break :
2500 VA with maximum of 5 A and 660 V AC
Insulation :
100W (Resistive), 50W(Inductive) with maximum of 5 A and 250 V DC
1) 2 KV RMS, 50Hz. For 1 minute / 2.5 KV for 1s. Between all terminals and case as per IEC 60255
2) 1 KV RMS, 50Hz. For 1 minute across open contacts as per IEC 60255
1) 2 KV RMS, 50Hz. For 1 minute / 2.5 KV for 1s. Between all terminals and case as per IEC 60255
2) 1 KV RMS, 50Hz. For 1 minute across open contacts as per IEC 60255
Operating temperature :
-10 deg To +55 deg. Celsius
MECHANICAL DESIGN
Case dimensions in mm
Relay type | Front face dimensions Width X Height in Sq.mm | Panel cutout dimensions Width X Height in mm Tolerance + 1/- 0 | Depth in mm |
---|---|---|---|
Single element relay | 96 | 92 X 92 | 115 |
Ordering Information
Relay type :
JRV 161
Number of Elements :
1 Element
Rated voltage :
24,30,48,110,220,250V DC or
63.5,110 or 230V, 50 Hz AC
Flag :
S/R, H/R, Forward flag, Reverse flag