INVERSE TIME NUMERICAL  NON-DIRECTIONAL INVERSE TIME CURRENT RELAYS WITH COMMUNICATION AND BROKEN CONDUCTOR & NEGATIVE SEQUENCE

INVERSE TIME NUMERICAL NON-DIRECTIONAL INVERSE TIME CURRENT RELAYS WITH COMMUNICATION AND BROKEN CONDUCTOR & NEGATIVE SEQUENCE

₹49,335.00
Product Code: JD 100-15

Time line :Products will be shipped within 3 weeks from the date of order

Stock In Stock
Viewed 8324 times

Available Options

Product Description

Features
  • Programmable CT secondary current for 1A / 5A rating
  • Programmable system rated frequency (50/60Hz)
  • Display of Primary current
  • Available in many variants to suite main and back-up over-current protection schemes
  • Available in both Low load and normal load configurations Choice of 6 IDMT curves and definite time with hi-set (two stage characteristics)
  • Cold load pick-up
  • MIPConS for preventing E/F element operation during single-phasing
  • Trip Coil Supervision Protection
  • Multi-short auto re-closer facility
  • Self supervision facility
  • Trip test facility
  • History of 200 latest comprehensive fault
  • Draw-out facility with inbuilt CT shorting
  • Standard dimension – 144mm x 144mm
  • Negative sequence & Broken conductor detection
Application
The JD100 relay provides time graded phase and earth fault protection of Transformer, Feeder & Capacitor bank. MODBUS/IEC103 standard communication protocol over RS485 facilitates interfacing the relay with SCADA systems and RS – 232 / USB communication port provided at the front of the relay allows engineers to program the relay easily. Certain advanced features such as Nega-ve sequence protection,Broken conductor, Cold load pickup, RAPID(Rapid automatic planned imbalance current detection), Local breaker backup and Auto reclose improves the selectivity, sensivity and stability of the Power system. automatic planned imbalance current detection), Local breaker backup and Auto reclose improves the selectivity, sensitivity and stability of the Power system.
PRINCIPLE OF OPERATION
Over current relaying principles

The relay measures the line current from each of the line CTs and if the current exceeds the set threshold, then relay extends a trip signal atier an operating time. The relay's “operating time” is determined by selecting “definite time” or one of the six “inverse time” characteristics. This principle of relaying is equallyapplicable to both line and earth fault protection elements (51N / 51G).

Cold load pick-up

This feature can be useful in providing better selectivity in the operation of over current relays, by preventing them from operating, during inrush phenomenon.

MIPConS - Management of Imbalance Phasor Control through Supervision

known as single- phasing)for certain strategic purposes, conventional earth fault relays in substa- tions would pick-up and trip the circuit breaker. This operation is considered by the engineers as an undesirable outcome of a planned current un-balance in the system. “MIPConS”, when enabled, automatically detects the single-phasing operation and restoration of 3-phase system. Consequently, the feature prevents “earth fault element” from extending trip command under single-phasing conditions.

Trip Test Facility

The trip test will facilitate testing of relay operation without applying the input current. The trip test is useful to test the panel wiring and operation of breaker without any current. The trip contact will operate instantaneously. The phase and earth fault alarm contact will not operated during the trip test.

Restricted earth fault protection

A simple earth fault protection may not provide adequate protection for transformer windings particularly when in the case of "Y" connected winding earthed with an impedance. The efficacy of protection is improved by employing restricted earth fault protection. The said protection scheme is prevalent even under the case of “solidly earthed systems”. High-impedance protection scheme requires the residual current derived from the three line CTs to be balanced with the "neutral current" derived out of neutral CT. This unit protection scheme is generally sensitive only to the fundamental harmonic component of the measured current and has an "instantaneous time" as its operating characteristics.

Auto re-close facility

Relay has a multi shot auto re-closer facilitates automation for breaker operation. Auto re-closer can be programmed to provide a maximum of five shots. “Dead time” starts when a trip signal is provided due to the occurrence of a fault involving L-L or L-G or L-L-G or L-L-L or L-L-L-G. Atier an elapse of a time interval equal to “dead time”, closing command will be extended. The “reclaim time” timer starts at the instant when the “dead time” timer expires. If atier extending the “breaker close” signal an over current fault was detected before the “reclaim time” timer reached its terminal count, then the relay understands that the fault in the system is still persisting and the over current relay will issue a trip signal. The relay tries to close the breaker for a maximum of the programmed number of shots before it chooses to lockout. The relay can be configured for independent trip sequence as IDMT or Definite time.

TCSR

TCSR monitors trip coil continuously. If the trip circuit (or any coil) that is being supervised develops a snag, then the supervision relay extends an alarm without a delay. The relay monitors the trip coil under all the states of a breaker viz. close, open and during transition. The underlying mechanism of supervision is to perform hi- impedance measurement across two input circuits appropriately wired along with trip coil, 52A and 52B auxiliary contacts. 1-NO & 1-NC contacts have been provided for the purpose of alarm and SCADA. The current rating of these contacts is 5Aat 24VDC / 230VAC.

Supervision functions

Self supervision feature allows the operator to take note of any internal failure in the relay. An LED and an output contact is provided for annunciation purposes.