Numerical, three pole, directional / non-directional, inverse definite time, 3 O/C or 2 O/C + 1 E/F relay with /without inst. highset
₹61,347.00
Product Code: JNP 096P/JNP 096
Time line :Products will be shipped within 3 weeks from the date of order
Stock In Stock
Viewed 5782 times
Categories
Cart
Account
Search
Recent View
All Categories
×
-
Products Category
- Earth Leakage Relays
- Electromechanical Auxiliary & High Speed Tripping Relays
- Electronic Hooters
- LED Indicating Lamps
- LED Semaphore Indicators
- Micro Processor Based Directional / Non-directional, Non-Communicable Current Relays
- MICRO PROCESSOR BASED INSTANTANEOUS / DEFINITE TIME AC VOLTAGE RELAYS
- Micro Processor Based Multi Shot, Auto Reclose Relays
- Micro Processor Based Neutral Earth Resistor Monitoring Relays
- Micro Processor Based PT Fuse Failure Relays
- MICRO PROCESSOR BASED RESTRICTED E/F RELAYS
- Micro Processor Based Trip Circuit Supervision Relays
- Numerical Check Synchronizing Relays
- Numerical Directional / Non-directional, Non-Communicable Current Relays
- Numerical Non-directional Inverse Time Current Relays Without Communication
- NUMERICAL OVERFLUX RELAYS
- Numerical Transformer Differential Relays
- Panel Accessories
- Push Buttons
- Semaphore Indicators
- Terminal Blocks & Plugs for Testing
- Time Delay Relays
- Two Stage Frequency Relays
- Micro Processor Based Inverse Time Non- Directional, Non-communicable Current Relays
- Non-directional Inverse Time Current Relays With/without Communication
- Micro Processor Based Inverse Time Non-directional, Non-communicable Current Relays
- Micro Processor Based Instantaneous / Definite Time Ac Voltage Relays
- Micro Processor Based Instantaneous / Definite Time Battery E/F Relays
- Micro Processor Based Instantaneous / Definite Time Current Relays
- Micro Processor Based Instantaneous / Definite Time Dc Voltage Relays
Shopping Cart
×
Your shopping cart is empty!
Search
×
Recent View Products
×
Product Description
Features
- Programmable characteristic angle
- Programmable operating characteristics
- High speed directional control
- Low Burden
- Trip test facility
- Choice of four inverse curve and definite time
- Programmable for directional /non-directional
- RS 232 communication port
- RS485 communication port (optional)
- History of 5 latest faults
- Self supervision facility
Application
The relay provides time graded directional phase
and earth fault protection of generators,
trasformers, capacitors, etc.
Principal of Operation
JNP 096/096P provides directional over current protection for power systems. The Relay operating time is determined by selectting definite time characteristics or one of the four inverse time
characteristics i.e. (3s normal inverse, 1.3s normal inverse, very inverse and extremely inverse).
The operating region is defined by the characteristic angle selected. The relay measures the
current and voltage from each of the phases and if the phase angle in the operating zone of the
relay, then the relay extends trip signal.
Ratings
Settings
OVER LOAD RATINGS
Current rating(In) :
1A / 5A
Voltage rating :
110V, 50Hz for Phase
63.5, 50Hz for E/F
63.5, 50Hz for E/F
Auxiliary supply :
1)20-60V DC
2)75 – 150V AC / DC
3)175 – 300V DC/ 185 – 250V AC
2)75 – 150V AC / DC
3)175 – 300V DC/ 185 – 250V AC
Inverse time curve :
1) 3 Sec normal inverse curve
2) 1.3 Sec normal inverse curve
3) Very inverse curve
4) Extremely inverse curve
2) 1.3 Sec normal inverse curve
3) Very inverse curve
4) Extremely inverse curve
Definite time :
0.1 to 25.0 Sec in steps of 0.1s
Directional Feature :
Separate Choice of Active / Inhibit mode for over current & Hi-set.
Characteristic Angle :
Phase - 30°, 45°, and 60° lead
E/F - 12.5°, 30° and 45° lag
E/F - 12.5°, 30° and 45° lag
Overcurrent setting :
Phase - 50 to 200% in steps of 5 %
E/F - 5 to 80% in steps of 1%
E/F - 5 to 80% in steps of 1%
TMS :
0.02 to 1.0 in steps of 0.01
(Separate for Phase & E/F)
(Separate for Phase & E/F)
Hi-set setting :
Choice of Active / Inhibit Mode
Phase - 200 to 3200% in steps of 100%
E/F - 50 to 800% in steps of 50%
Phase - 200 to 3200% in steps of 100%
E/F - 50 to 800% in steps of 50%
Programmable Reset Mode :
Hand / Self Reset
AC current input :
2 times Rated continuous
20 times Rated for 3 secs.
40 times Rated for 1 sec.
20 times Rated for 3 secs.
40 times Rated for 1 sec.
Burden
Accuracy
Contact Ratings
Contact Durability
Insulation
AC Current Input :
0.1VA per phase (rated 5A)
0.05VA per phase(rated 1A)
0.05VA per phase(rated 1A)
AC Voltage input:
2VA for all phases and E/F
Auxiliary supply :
Less than 4W(Non operated)
Less than 10W(Operated)
Less than 10W(Operated)
Protection :
+/- 5%
Operating time :
+/- 5%
Output contacts :
0A at 24V DC / 230V AC
Loaded contact :
10,000 operations minimumt
Unloaded contacts :
100,000 operations minimum
- 2KV RMS, 50 Hz for 1 minute / 2.5 KV for 1 sec .
Between all terminals and earth. - 1KV RMS, 50 Hz for 1 minute across open contacts.
Weight :
App. 7 Kgs.
Case Size :
Fascia 152 x 296 mm, Depth 250 mm
Installation :
Flush mounting
Panel cutout :
146 x 264 mm
Terminal Diagram
Ordering Information
Current rating :
1A or 5A
Relay type:
1) JNP 096 (2O/C + E/F)
2) JNP 096P (3O/C)
2) JNP 096P (3O/C)
Auxiliary Supply :
20 to 60V DC
75 to 150V DC
175 to 300V DC / 185 to 250V AC
75 to 150V DC
175 to 300V DC / 185 to 250V AC